The Eaton 93E UPS is three-phase, double-conversion online UPS that helps you address your biggest data center challenges: operating costs, remote management and unplanned downtime. With internal batteries that provide up to 21 minutes of runtime and a 7 percent higher efficiency rating than competitive units, the 93E UPS maximizes the protection you get for every square foot of floor space and every utility dollar you spend. A detachable maintenance bypass with a mean time to repair of <30 minutes and enhanced management and monitoring capabilities from Brightlayer Data Centers suite increase the reliability of the system and the amount of control you have without even setting foot in the data center.
Lowest total cost of ownership
Guarantee zero downtime
Maximize runtime with batteries
Save floor space
Product snapshot
20-60 kVA
208/220 Vac Three-phase
50/60 Hz
Double conversion online with Multi-Mode (High efficiency)
98% in high efficiency mode
Tower
Internal batteries up to 60 kVA
External batteries up to 400 kVA
Input characteristics
20 kVA/16 kW
30 kVA/24 kW
40 kVA/32 kW
60 kVA/48 kW
208/120V, 4 wire
220/127V, 4 wire
+20% / -15% at 208V with 100% load without depleting battery
50/60 Hz (40 to 72 Hz)
> 0.99 typical
5% THD
Output characteristics
208/220, 3/4 wire
±1% static, ±5% dynamic at 100% resistive load change, <20 ms response time
Battery
9 AH, sealed, lead-acid, maintenance free
20 kVA – 21 minutes
30 kVA – 12 minutes
40 kVA – 10 minutes
60 kVA – 5 minutes
ABM or float technology
EBC runtimes
21
138
12
84
12
128
6.6
77
Interactive battery runtime graphs
Dimensions and weights (mm/inches)
53.5 in/1360 mm
20.9 in/530 mm
31.5 in/800 mm
1049.4 lbs/ 476 kg
74.9 in/1880 mm
23.6 in/600 mm
31.5 in/800 mm
1499.1 lbs/ 680 kg
General characteristics
Up to 98% on high-efficiency mode
Up to 92% on double-conversion
Automatic on overload or UPS failure
102-110% for 10 minutes
111-125% for 30 seconds
>/=126% for 150 milliseconds
>/=150% for 40 milliseconds
Short circuit conditions: current limit at 2.5x nominal FL current for 60 milliseconds.
102-110% for 10 minutes
111-125% for 30 seconds
>/=126% for 150 milliseconds
>/=150% for 40 milliseconds
Short circuit conditions: immediate transfer to bypass; then 115% continuous, with transient capability of 20x nominal for 10 milliseconds.
102-110% for 10 minutes
111-125% for 30 seconds
>/=125%: current limited at 125% for 30 seconds
Communications
Graphical LCD with blue backlight
(4) LEDs for notice and alarm
Yes
(1) RS-232
(1) REPO
(2) Mini-slot communication bays
(3) Building inputs
Environmental characteristics
0ºC (32ºF) to +30ºC (86ºF);
Batteries recommended max. +25ºC (77ºF)
-25ºC (-13ºF) to +55ºC (131ºF) without batteries
+15ºC (59ºF) to +25ºC (77ºF) with batteries
5-95%, non-condensing
<65 dBA at 1 meter (noise less room) typical
< 1500m at +30°C (86ºF)
Certifications
EN55022/EN55024
IEC 62040-2
ISO 9001: 2000 and ISO 14001: 1996
UL, cUL